![SKF KFG Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/skf/kfg/kfg_assembly-instructions-manual_1287056034.webp)
Page 34
EN
4.5.3.5 Connectivity for timer operation
without system monitoring
Connector pin assignment in timer operation
PIN Code
Assignment
1
M
- Supply voltage potential (0 V, GND)
2
L+
+ Supply voltage potential "Main machine switch ON"
3
DK
Pushbutton "1st Interim lubrication" "2nd Delete fault notiication"
4
SL2
Indicator light "fault"
5
PS
Pressure switch " + "
6
PS
Pressure switch "signal"
7
SL1
Indicator light "pump ON"
4.5.3.6 Connectivity for timer operation
with system monitoring
(single-line centralized lubrication system)
Programming: tPA, tCO, COP = OFF
1
BN
KFGS...
F
2
3
4
5
6
7
X1
R
D
-BK
BU
PK
V
T-
G
N
DK
SL2
2,4 W
M
L+ (Industrie)
SL1
2,4 W
1
BN
KFGS...
F
2
3
4
5
6
7
X1
R
D
-BK
BU
PK
V
T-
G
N
DK
SL2
2,4 W
SL1
2,4 W
BK
BK
PS
+
M
L+ (Industrie)
Programming: tPA, tCO, COP = PS
Timer mode
In timer mode, the interval time is determined
by a time value. It is conigured by entering a
time value in hours.
The pump cycle time is conigured using a time
value in minutes.
The ill level monitoring unit (W1 control) is
internally connected to the integrated pump
control unit. A fault notiication can be sent to
the process control level via indicator light SL2.
Settings for single-line lubrication
K
F
G
S
Assembly instructions