TXP CLC Course
11
Total drive run time (TGL)
Name: TGL
Function: Defines the total run time of the drive between the limit positions after a
command output, for alarm and indication (only effective with both RWE and
RWA set at 3)
Range of values: 0 to 60,000
Meaning:
0 = no run time monitoring
60,000 = 6,000 s (adjusting steps: 0.1 s)
Default setting:
10 = 1 s
Effect of Feed-back message on command execution
Name: WRBHAEA; WRBHAAZ; WRBSEA; WRBSAZ
Function: Defines whether manual, automatic and protection On and Off
commands are to be blocked when a feed-back fault is active in the command
direction
Range of values: blocked/not blocked
Meaning:
blocked = blocks command execution
not blocked = command is executed
WRBHAEA = MANUAL/AUTOMATIC ON blocked/not blocked
WRBHAAZ = MANUAL/AUTOMATIC OFF blocked/not blocked
WRBSEA = PROTECTION ON blocked/not blocked
WRBSAZ = PROTECTION OFF blocked/not blocked
Basic setting: blocked
Effect of status discrepancy/monitoring
Name: WEFSPERR; WEFNSEA; WEFNSAZ
Function: Defines whether limits are monitored and if the protection On and Off
commands should be blocked when a status discrepancy fault is detected
Range of values: blocked/not blocked
Meaning:
WEFSPERR = blocked status discrepancy monitoring disabled
WEFSPERR = not blocked status discrepancy monitoring enabled
WEFNSEA = PROTECTION ON command blocked/not blocked
WEFNSAZ = PROTECTION OFF command blocked/not blocked
Basic setting: blocked
Slowing-down time for travel-dependent disconnection (NLZ)
Name: NLZ
Function: Defines how long the command output signal is maintained after the
feedback input signal is received for torque close or open.
Range of values: 0 to 100
Meaning:
0 = no delayed disconnection
100 = 10 s disconnection delay
Basic setting:
0
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
15
Содержание TXP-CLC
Страница 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Страница 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Страница 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Страница 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Страница 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Страница 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Страница 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Страница 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Страница 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Страница 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Страница 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Страница 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...