TXP CLC Course
11
Last status reached by protection (ZES)
This output is a logic “1” when the last command output was initiated by
protection.
Last status reached by automatic (ZEA)
This output is a logic “1” when the last command output was initiated by
automatic.
Last status reached by manual (ZEH)
This output is a logic “1” when the last command output was initiated by the
operator.
Under voltage time running (USZ)
This output is a logic “1” when the under voltage input (UGS) is a logic “1” and
the timer has not timed out.
Under voltage limit signal (ULS)
This output is a logic “1” when the under voltage input (UGS) is a logic “1” and
the timer has timed out.
Feeder ready for operation (AZB)
This output is a logic “1” when the feeder not ready for operation input (ANB) is a
logic “0” and the breaker or switchgear is in test position or racked out.
No Status discrepancy (NOSD)
This output is a logic “1” when there is no status discrepancy fault. It is a logic “0”
when there is a fault condition for the FB 163. A status discrepancy is present if
the actual status changes without a corresponding command (actual status
≠
command memory). It is assumed that the new actual position has been signaled
by non-faulty feedback messages.
No feeder fault (NOFF)
This output is a logic “1” when the feeder fault input (SAG or SGF) is a logic
“1”.This would indicate a trip condition or over current event in the motor starter.
No running time / torque alarm (KLB)
This output is a logic “1” when there are no run time faults (TUM or TWS) and the
torque inputs are a logic “0”.
Feedback not on/open (CB/ONN)
This output is a logic “1” when there is no feed back on input (RWE or FB/ON).
Feedback not off/closed (CB/OFFN)
This output is a logic “1” when thee is no feed back off input (RWE or FB/ON).
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
21
Содержание TXP-CLC
Страница 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Страница 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Страница 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Страница 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Страница 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Страница 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Страница 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Страница 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Страница 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Страница 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Страница 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Страница 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...