![Siemens TXP-CLC Скачать руководство пользователя страница 51](http://html.mh-extra.com/html/siemens/txp-clc/txp-clc_manual_376943051.webp)
TXP CLC Course
5
Figure 3 shows the overall structure of the KKS mounting location, but in most
cases the numbers used within the drawings are abbreviated in some form or
another. The following list provides some other examples of mounting locations
that are commonly used in the I&C manuals:
+CJP02
This type of number is normally used to identify the cabinet. It can
be found in the drawing title block or on the drawing itself. The
prefix "+” in this case represents the unit number in which this
drawing pertains.
+.DC015
This type of number is used to identify a module. The prefix "+” in
this case represents both the Unit and the cabinet number. The
cabinet number in these cases can be found in the title block of the
drawing.
+.XD007
This type of number is used to identify a Termi-point connection.
Below this number the letters A to H would be listed to show
connection points for the individual signal. The prefix "+" in this
case represents both the Unit and the cabinet number in which the
termi-point is physically located. The cabinet number in these cases
can be found in the title block of the drawing.
KKS Function Codes
Some of the most common KKS Function Codes that are used for the
Combustion Turbine are listed below. In some cases the descriptions for the KKS
function codes that are assigned to the combustion turbine may not fit the official
KKS description. In these cases the combustion turbine description will be used.
A – Grid and distribution system
ADA
High Voltage Switchgear
AEA
138 kV system
AFA
69 kV system
B - Power transmission and auxiliary power supply
BA
Power
transmission
BAA
Generator
leads
BAB
Foundation
cabinets
BAC
Generator
Circuit Breaker
BAT
Generator
transformers
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
5
Содержание TXP-CLC
Страница 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Страница 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Страница 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Страница 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Страница 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Страница 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Страница 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Страница 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Страница 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Страница 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Страница 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Страница 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...