TXP-CLC
Course
8
Parameters
AI/SIG
This analog output is the value of the analog input signal, after all internal
processing, that is available for further processing in the AP logic.
GS1
This binary output is the value of the first binary limit signal, after all internal
processing, that is available for further processing in logic. It is based on the limit
value parameter (LV1) and the analog input value (AI/SIG) qualified by the
hysteresis parameter (HYS) and all other parameters that are indicated by the
number 1 in there short name (GSB1, ULLL1, EGSW1, and EGS1).
GS2
This output is the value of the second binary limit signal, after all internal
processing, that is available for further processing in logic. It is based on the limit
value parameter (LV2) and the analog input value (AI/SIG) qualified by the
hysteresis parameter (HYS) and all other parameters that are indicated by the
number 1 in there short name (GSB2, ULLL2, EGSW2, and EGS2).
GS3
This output is the value of the third binary limit signal, after all internal
processing, that is available for further processing in logic. It is based on the limit
value parameter (LV3) and the analog input value (AI/SIG) qualified by the
hysteresis parameter (HYS) and all other parameters that are indicated by the
number 1 in there short name (GSB3, ULLL3, EGSW3, and EGS3).
GS4
This output is the value of the fourth binary limit signal, after all internal
processing, that is available for further processing in logic. It is based on the limit
value parameter (LV4) and the analog input value (AI/SIG) qualified by the
hysteresis parameter (HYS) and all other parameters that are indicated by the
number 1 in there short name (GSB4, ULLL4, EGSW4, and EGS4).
KSIM
This output is a logic “1” when the analog input signal is being simulated by
means of software simulation or when the signal is the default set by parameter
EASW.
KG
This output is a logic “1” when the analog input signal is valid.
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
5
Содержание TXP-CLC
Страница 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Страница 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Страница 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Страница 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Страница 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Страница 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Страница 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Страница 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Страница 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Страница 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Страница 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Страница 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...