![Siemens TXP-CLC Скачать руководство пользователя страница 129](http://html.mh-extra.com/html/siemens/txp-clc/txp-clc_manual_376943129.webp)
TXP-CLC
Course
8
MOD
This parameter defines whether the input signals are processed mathematically,
and how. Square root calculation are only used for positive values.There are 9
possible choices in the parameter mask: 0 - 8
Meaning:
0 = no modification
1 = square-rooting from 0 to 110 % (complete measuring range)
2 = square-rooting from 5 to 110 %, range 0 to 5 % = ”0”
3 = square-rooting from 10 to 110 %, range 0 to 10 % = ”0”
4 = Multiplication (with correction factor)
5 = Multiplication followed by square-rooting from 0 to 110 %
6 = Multiplication followed by square-rooting from 5 to 110 %
7 = Multiplication followed by square-rooting from 10 to 110 %
8 = Multiplication by square-rooted correction factor
The default setting is 0
LV1
This parameter is the limit value, in engineering units,) of the first binary output.
LV2
This parameter is the limit value, in engineering units, of the second binary
output.
LV3
This parameter is the limit value, in engineering units, of the third binary output.
LV4
This parameter is the limit value, in engineering units, of the fourth binary output.
HYS
This parameter defines the range, in engineering units, between triggering and
resetting of the limit signals. The default setting is 5.
ABZE
This parameter defines the sampling period for generation of the signal change
report (TTD) to the Operating and Monitoring (OM) system. A TTD is only
generated if a downward or upward violation of the delta parameter (DELT) has
occurred. The range of values that can be used are 250 to 60000.
The default setting is 1000 (1 s)
DELT
This parameter defines how much of a change of the analog input signal is
required in order for a TTD to be generated. The default setting is 0
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
7
Содержание TXP-CLC
Страница 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Страница 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Страница 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Страница 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Страница 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Страница 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Страница 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Страница 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Страница 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Страница 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Страница 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Страница 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...