![Siemens TXP-CLC Скачать руководство пользователя страница 84](http://html.mh-extra.com/html/siemens/txp-clc/txp-clc_manual_376943084.webp)
TXP CLC Course
2 Structure
diagrams
2.1
Equipment structure diagrams
One and only one equipment structure diagram (topology) must exist for each
project. It depicts all TXP components that are connected to the LAN and
supports automatic allocation of consistent bus addresses.
The ID--code ”YDH = OVE001V001” could be used for a topology. The FGC for
the topology must exist but has no significance. The name for AS Structure
diagram (YDM) is determined from the LAN symbol parameters. The ID code
YDM + 00CJF01 could be used for an AS structure drawing. If a YDM diagram
does not exist it can be created automatically, and the system allows navigation
to it from the topology. The AS structure diagram can be accessed for example
via the LAN symbol on the topology.
Function block parameter mask entries must always be followed by the enter
key, otherwise the entries will not be saved. All symbols on each drawing must
be connected with a connecting line in a from / to manner.
When the topology is saved, the top.ed program is called automatically to
analyses the LAN structure and assigns addresses and sequential numbers to all
components that are not already assigned.
2.2
AS structure diagram
The AS structure diagram shows the cabinet level structure of the components
on the topology diagram. The YDM diagram is function related and is therefore
assigned a function group code (e.g.: YPAC01). Each element of this diagram
corresponds to a rack level diagram (YDR) that shows an individual rack with it’s
module configuration.
The ID code for the rack diagram is a mounting location within the equipment ID
code (cabinet name), a dot must be entered for the first character of the
mounting location (e.g.: 00CJF01.BG).
2.3
Individual level structure diagram
The rack structure diagram shows the racks and the individual modules. The part
numbers and Input Output (I/O) ID codes and signal ID codes are entered in the
parameter mask for I/O assignments.
After code generation, navigation will be possible from the YDR drawings to the
associated rack level “measurement” logic drawings (YFR).
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
2
Содержание TXP-CLC
Страница 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Страница 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Страница 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Страница 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Страница 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Страница 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Страница 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Страница 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Страница 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Страница 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Страница 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Страница 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...