PIN
Signal name
Signal type Meaning
8
-
-
Reserved, do not use
A
+ (24 V)
VO
Voltage supply for DRIVE-CLiQ, 450 mA maximum
B
M (0 V)
VO
Ground to 24 V
Signal type: I = Input; O = Output; VO = Voltage Output
Position of the DRIVE-CLiQ interfaces
B
A
8
1
Figure 8-3
DRIVE-CLiQ interfaces
Cable specification
Table 8-6
Cable specification for X100 - X103
Characteristic
Version
Connector type
RJ45 socket
Cable type
DRIVE-CLiQ standard (inside the control cabinet)
MOTION-CONNECT (outside the control cabinet)
Max. cable length
70 m
8.6.2
Connectable DRIVE-CLiQ components
Components
As a rule, all SINAMICS/SIMOTION components approved for SINUMERIK can be connected to an
NCU using DRIVE-CLiQ.
Table 8-7
Components with DRIVE-CLiQ
Component
Description
NX10.3 / 15.3
Drive expansion module for up to 6 axes
SINAMICS S120, system components, booksize format
Connecting
8.6 DRIVE-CLiQ components