NOTICE
Damage to the module
If the outputs are overloaded, the heat can melt the contacts.
Therefore, for a demand factor of 100%, a max. current of I
out
= 0.25 A at X111, X222, X333:
Pin 2, must not be exceeded.
Technical data
Table 12-25 Electrical specification of the digital outputs
Digital outputs
min.
Standard
max.
Nominal
High-level voltage (U
H
)
V
CC
- 3 V
1)
V
CC
24 V
Output current I
OUT
-
-
250 mA
2)
-
Voltage with low level (U
L
)
-
-
-
Output open
Leakage current at low level
-
50 μA
400 μA
-
Signal delay time T
PHL
-
0.5 ms
-
-
Maximum switching frequency
Resistive load
-
-
100 Hz
-
Inductive load
-
-
2 Hz
-
Lamp
-
-
11 Hz
-
1) U
H_typical
= V
CC
- I
OUT
× R
ON
V
CC
: Current operating voltage
I
OUT
: Output current
Maximum short-circuit current: 4 A (max. 100 μs, V
CC
= 24 V)
R
ON
: Maximum internal resistance = 0.4 Ω
2) For a simultaneity factor of 100% (all outputs active)
Incorrect connection causes neither high level nor destruction of the outputs.
12.2.4
Parameterization
12.2.4.1
Input / output images
Input image
The image comprises 2 slots (n, d ≙ start address):
• Slot 1: Digital inputs (DI)
– n+0 … n+8 (9 byte)
– X222.P3 - .P10 are rapid inputs
• Slot 2: Diagnostics: d+0 .. d+1
Connectable components
12.2 PP 72/48D PN
NCU 1740
124
Equipment Manual, 10/2021, A5E51087503B AA
Содержание SINUMERIK ONE NCU 1740
Страница 48: ...Dimension drawings 6 1 NCU 1740 dimension drawing NCU 1740 48 Equipment Manual 10 2021 A5E51087503B AA ...
Страница 52: ...Installation 7 4 Mounting the NCU without spacers NCU 1740 52 Equipment Manual 10 2021 A5E51087503B AA ...
Страница 96: ...Technical data 11 3 Recycling and disposal NCU 1740 96 Equipment Manual 10 2021 A5E51087503B AA ...
Страница 156: ...Connectable components 12 3 PP 72 48D PN 2 2A PN NCU 1740 156 Equipment Manual 10 2021 A5E51087503B AA ...
Страница 160: ...Safety symbols NCU 1740 160 Equipment Manual 10 2021 A5E51087503B AA ...