• Tenir compte du rayon de courbure admissible des câbles.
• Pose les câbles de manière à ce qu’ils ne pincent pas les câbles.
• Pose les câbles en évitant tout contact avec des arrêtes abrasives.
Note
When connecting an external 24 V DC power supply to the interfaces, this must satisfy the
requirements of a protective extra low voltage (PELV) according to UL 61010. A series fuse must
also be used which reliably trips within 120 seconds at an ambient temperature of 0 °C when a
short-circuit occurs.
For a primary supply of the power supply used from OVC III circuits up to 600 V AC (line to neutral
voltage), it must be ensured that the contact gap of the fuse – or the individual fault-proof circuit
– is 3.0 mm according to UL 61010.
When using an external power supply, ensure that the fuse used has a trip rating that
corresponds to the maximum possible short-term short-circuit current of the power supply unit
being used.
Table 8-2
X124 interface
Characteristics
Version
Connector type
4-pin screw-type terminal
Number of cables that can be connected
1
Connectable cable types and conductor cross-sec‐
tions
Rigid
1.3 mm² … 2.5 mm²
Flexible
1.3 mm² … 2.5 mm²
Flexible, with end sleeve without plastic
sleeve
1.3 mm² … 2.5 mm²
Flexible, with end sleeve with plastic sleeve
1.3 mm² … 2.5 mm²
AWG/kcmil
16 ... 14
Stripped length
6 … 7 mm
Tool
Screwdriver 0.5 x 3 mm (M2.5)
Tightening torque
0.4 to 0.5 Nm
Max. current carrying capacity, incl. loop-through
20 A
*)
(15 A according to UL/CSA)
Max. cable length
10 m
*)
This value must be taken into consideration for the current-carrying capacity of the power supply cable.
The following cable lugs may be used:
• Crimped cable lug to DIN 46234
• Pressed cable lug to DIN 46235
• Tube-type cable lug to SN 71322
• Tube-type cable lug "Klauke R Series", UL Category ZMVV
Connecting
8.5 Power supply
NCU 1740
Equipment Manual, 10/2021, A5E51087503B AA
61
Содержание SINUMERIK ONE NCU 1740
Страница 48: ...Dimension drawings 6 1 NCU 1740 dimension drawing NCU 1740 48 Equipment Manual 10 2021 A5E51087503B AA ...
Страница 52: ...Installation 7 4 Mounting the NCU without spacers NCU 1740 52 Equipment Manual 10 2021 A5E51087503B AA ...
Страница 96: ...Technical data 11 3 Recycling and disposal NCU 1740 96 Equipment Manual 10 2021 A5E51087503B AA ...
Страница 156: ...Connectable components 12 3 PP 72 48D PN 2 2A PN NCU 1740 156 Equipment Manual 10 2021 A5E51087503B AA ...