Name
Designation
Color
Description
Flashes 0.5 Hz: System software running, RUN state
H3
PNFault
Red
Not lit: Module is operating without errors; data exchange with all configured IO devices
is running.
Lit: Serious bus fault; only output when one of the following errors is detected for the ports:
● No physical connection to a subnet/switch
● Incorrect transmission rate
● Full duplex transmission is not activated
7.1.2
Mounting
Call sequence
The recommended installation of the MCP 483C PN machine control panel is shown in the
following figure:
338
0&3&31
Mounting positions
The permitted mounting position is max. 60° to the vertical.
Note
For mounting positions greater than 60°, a fan must also be installed to keep the ambient
temperature of the machine control panel constantly below 55 °C.
Tension jacks
The machine control panel is mounted from the front in a rectangular cut-out and attached by
means of nine supplied tension jacks (0.5 Nm tightening torque).
Tension jacks are also available as a spare part (see Section: "Spare parts and accessories
Connectable components
7.1 MCP 483C PN
PPU
Manual, 01/2014, 6FC5397-2DP40-3BA3
97