Table 7-104 Overview of messages as a function of the "alive and well" counter
"alive and
well" counter
Value
byte 1
Message
0
0
Reserved
1
Temperature value
2
0
No error
1
Impermissible input voltage in temperature measurement mode
2
Reserved
3
Overload at the outputs
4
Incorrect operating mode selection
5
Internal error, system error
6
Overrange at the inputs
7
Overrange at the outputs
3 ... 7
0
Reserved
Table 7-105 Elimination of error at "alive and well" counter status "2"
Value
byte 1
Cause
Effect
Remedy
1
In the temperature
measurement operating
mode, an input voltage is too
high. The hardware may
become damaged/
destroyed as a result.
The "PNFault" LED is activated.
The outputs are disabled.
1)
The value 0x80 is stored in Status Byte
1.
It is essential that a Pt100 element is
connected to terminals 3-4 or 7-8.
The module must be restarted with
Power ON following elimination of the
error.
2
Reserved
-
-
3
Overload at the outputs
The "PNFault" LED is activated.
The outputs are disabled.
1)
The value 0x80 is stored in Status Byte
1.
Check the loads at the analog output.
The module must be restarted with
Power ON following elimination of the
error.
4
Incorrect operating mode
selection, e.g. temperature
measurement at the analog
outputs.
Selection of operating mode is rejected, If selected correctly, the module switches
to cyclic operation.
5
Internal error, system error
The "PNFault" LED is activated.
The outputs are disabled.
1)
The value 0x80 is stored in Status Byte
1.
The firmware has detected a system
error, this status can only be exited by
means of a switch-on / switch-off.
6
Overrange at the inputs
Check input circuit and adjust, if required.
7
Overrange at the outputs
Correct values in the user program.
1)
The analog outputs retain their last specified value.
Diagnostics via Status Bytes 0/1
In Status Byte 0, the set operating modes are reflected e.g. "0x55" if Control Byte 0 = 0x55
has been specified.
In the event of an error, the error bit is set in Status Byte 1 (bit 7). In the event of an error in
one channel, all channels are disabled.
Connectable components
7.7 PP 72/48D 2/2A PN
PPU
206
Manual, 01/2014, 6FC5397-2DP40-3BA3
Содержание SINUMERIK 828D PPU Series
Страница 12: ......
Страница 34: ......
Страница 42: ......
Страница 52: ......
Страница 92: ......
Страница 150: ... r r r Connectable components 7 4 Electronic handwheel PPU 150 Manual 01 2014 6FC5397 2DP40 3BA3 ...
Страница 224: ......
Страница 226: ......
Страница 240: ......
Страница 244: ......