Appendix
A.7 Setting a non standard SSI encoder
Converter with control units CU250D-2
380
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Parameter Description
p0437[1]
Sensor Module configuration extended (Factory setting: 0000 0000 0000 0000 0000 1000 0000 0000 bin)
Bit
Signal name
1 signal
0 signal
00
Data logger
Yes
No
01
Zero mark edge detection
Yes
No
02
Correction position actual value XIST1
Yes
No
04
Edge evaluation bit 0
Yes
No
05
Edge evaluation bit 1
Yes
No
06
Freeze the speed actual value for dn/dt errors
Yes
No
11
Fault handling after PROFIdrive
Yes
No
12
Activate additional messages
Yes
No
13
Support absolute position for incremental encoder
Yes
No
26
Deselect track monitoring
Yes
No
p0438[1]
Squarewave encoder filter time
(Factory setting: 0.64 [μs])
0
No filtering
p0439[1]
Encoder ramp-up time (Factory setting: 0 [ms])
p0446[1]
Encoder SSI number of bits before the absolute value (Factory setting: 0)
p0447[1]
Encoder SSI number of bits absolute value (Factory setting: 25)
p0448[1]
Encoder SSI number of bits after the absolute value (Factory setting: 0)
p0449[1]
Encoder SSI number of bits, filler bits (Factory setting: 1)
Sets the number of filler bits for double absolute value transfer in the SSI protocol.
This parameter is only of significance for p0429.2 = 1.
r0452[1]
Squarewave encoder filter time display
p0453[1]
Pulse encoder evaluation zero speed measuring time (Factory setting: 1000 [ms])
If no pulses are detected from track A/B during this time, a speed actual value of zero is output.
This function is required for slow-running motors so that actual speeds close to zero can be output correctly.
For further information, please refer to the List Manual.