Alarms, faults and system messages
10.6 List of alarms and faults
Converter with control units CU250D-2
332
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
10.6
List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 10- 6 Faults, which can only be acknowledged by switching the converter off and on again (power on reset)
Number Cause
Remedy
F01000
Software fault in CU
Replace CU.
F01001
Floating Point Exception
Switch CU off and on again.
F01015
Software fault in CU
Upgrade firmware or contact technical support.
F01018
Power-up aborted more than once After this fault is output, the converter powers up with the factory settings.
Remedy: Back up factory setting with p0971=1. Switch CU off and on
again. Recommission the converter.
F01040
Parameters must be saved
Save parameters (p0971).
Switch CU off and on again.
F01044
Loading of memory data card de-
fective
Replace memory card or CU.
F01105
CU: Insufficient memory
Reduce number of data records.
F01205
CU: Time slice overflow
Contact technical support.
F01250
CU hardware fault
Replace CU.
F01512
An attempt has been made to
establish an conversion factor for
scaling which is not present
Create scaling or check transfer value.
F01662
CU hardware fault
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
F30022
Power Module: Monitoring U
CE
Check or replace the Power Module.
F30052
Incorrect Power Module data
Replace Power Module or upgrade CU firmware.
F30053
Error in FPGA data
Replace the Power Module.
F30662
CU hardware fault
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
F30664
CU power up aborted
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
F30850
Software fault in Power Module
Replace Power Module or contact technical support.