Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Converter with control units CU250D-2
92
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Status word 1 (ZSW1)
Table 6- 3
Status word 1 when the basic positioner is active
Bit Meaning
Comments
P No.
Telegram 110
Telegram 111
0 1 = Ready to start
Power supply is switched on; electronics initialized; pulses are
inhibited.
p2080[0] =
r0899.0
1 1 = Ready
Motor is switched on (ON command = 1); no fault is active.
With the command "Enable operation" (STW1.3) the converter
switches on the motor.
p2080[1] =
r0899.1
2 1 = Operation enabled
Motor follows setpoint. See control word 1, bit 3.
p2080[2] =
r0899.2
3 1 = Fault present
The converter has a fault. Acknowledge fault using STW1.7.
p2080[3] =
r2139.3
4 1 = OFF2 inactive
Coast down to standstill is not active.
p2080[4] =
r0899.4
5 1 = OFF3 inactive
Quick stop is not active.
p2080[5] =
r0899.5
6 1 = Closing lockout active
It is only possible to switch on the motor after an OFF1 com-
mand and an additional ON command.
p2080[6] =
r0899.6
7 1 = Alarm present
Motor remains switched on; no acknowledgment necessary.
p2080[7] =
r2139.7
8 1 = Following error in tolerance
The actual difference between the actual position and the posi-
tion setpoint is within the permissible tolerance p2546.
p2080[8] =
r2684.8
9 1 = Control requested
The automation system is requested to accept the control from
the converter.
p2080[9] =
r0899.9
10 1 = Position setpoint reached
The axis has reached the position setpoint.
p2080[10] =
r2684.10
11 1 = Reference point set
The axis is referenced.
p2080[11] =
r2684.11
12 0
→ 1 = Acknowledgement, traversing
block active
---
p2080[12] =
r2684.12
13 1 = Axis is at a standstill
The absolute speed is less than p2161.
p2080[13] =
r2199.0
14 Reserved
1 = Axis acceler-
ates
---
p2080[14] =
r2684.4
15 Reserved
1 = Axis brakes
---
p2080[15] =
r2684.5