Advanced commissioning
7.6 Basic positioner and position control
Converter with control units CU250D-2
182
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
7.6.6.2
Following error monitoring
Description
The following error is the deviation between the position setpoint and the position actual
value while the converter is positioning the axis.
Figure 7-32 Monitoring the following error
The converter reports fault F07452 if the following error is too high. If you set the tolerance
to 0, monitoring is deactivated.
Setting following error monitoring
Precondition
You have selected the "Monitoring" screen and the "Following error monitoring" tab.
Procedure
To set the monitoring of the following error, proceed as follows:
1.
Set the monitoring window.
Start with the factory setting value.
Test your setting by positioning the axis at maximum velocity, e.g. from the control panel.
If the converter stops the travel with fault F07452 , you will need to either increase the
monitoring window or increase the dynamics of the position controller.