09.2008
Functions
Siemens AG
6SE7087-6QX70 (Version AK)
SIMOVERT MASTERDRIVES
Compendium Motion Control
7-69
3. Set the characteristic to meet requirement "Maximum torque in field
weakening range remains constant":
The output voltage (r003) at the field weakening activation speed
under no load conditions must be measured. The output voltage at
the end point of the desired field weakening range must then be
calculated according to the following formula from the maximum
converter output voltage (depends on converter supply voltage) and
the calculated output voltage at the field weakening activation
speed:
(
)
speed
activation
weakening
field
nd
a
speed
eakening
w
field
final
between
Ratio
:
range
weakening
Field
n
n
k
speed
activation
weakening
field
at
voltage
Output
U
range
weakening
field
of
end
at
oltage
v
Output
U
)
V
540
UDCL
when
(
V
350
U
where
k
U
k
1
U
U
Act
End
f
nAct
Out
Conv
nEnd
Out
Conv
max
Conv
2
f
2
nAct
Out
Conv
2
f
2
max
Conv
nEnd
Out
Conv
=
=
=
=
=
⋅
+
−
⋅
=
The formula is based on the simplified principle that the voltage drop
across the winding resistance of the motor is negligible in the field
weakening range. This applies to series 1FT6 and 1FK7 servo
motors.
The output voltage calculated by this formula must then be set at the
end speed of the field weakening range at no load via the short-
circuit current. The current setting must be increased in relation to
the automatically calculated value, as the automatic arameterization
run defines the short-circuit current for operation at constant
maximum output.
1FT6086 - 8AF71
Field
weakening
activation point
0
10
20
30
40
50
60
70
80
90
100
0
500
1000
1500
2000
2500
3000
3500
4000
4500
Speed [min-1]
Torque [Nm]
e.g. 1FT6086-8AF71, 27.5 Nm at 2900 rev/min to 4500 rev/min,
U
(no load 2900)
= 296 V, U
(no load 4500)
= 174 V I
k
(P105) = 60 A
Содержание simovert masterdrives
Страница 1: ...Compendium Edition AN simovert masterdrives Motion Control ...
Страница 2: ......
Страница 13: ......
Страница 197: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 32 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 199: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 34 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 201: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 36 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 203: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 38 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 205: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 40 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 207: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 42 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 209: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 44 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 947: ...08 2012 Siemens AG 6SE7087 6QX70 Version AN SIMOVERT MASTERDRIVES Compendium Motion Control Function Diagrams ...
Страница 1160: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control General parameter list ...
Страница 1416: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control Connector list ...
Страница 1446: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control Binector list ...
Страница 1466: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control List of function data set parameters ...
Страница 1471: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control List of binector data set parameters ...
Страница 1535: ......
Страница 1536: ......
Страница 1537: ......
Страница 1538: ......
Страница 1539: ......
Страница 1540: ......
Страница 1541: ......
Страница 1542: ......
Страница 1543: ......
Страница 1546: ......