Parameter
Description
Data
Read/write
of the motor encoder can be read off at r286 (also
see P549).
Further values for future use!
P116*
1FW3 ratio
116
This parameter defines the transmission ratio between the
motor and the encoder in the case of 1FW3 torque
motors.
The transmission ratio is indicated as a quotient.
Index 1 defines the revolutions of the motor shaft
(numerator) during simultaneous revolutions of the
encoder shaft in Index 2 (denominator).
P116.01
Transmission ratio = -----------
P116.02
The absolute value of P116.01 must be less or equal to
the absolute value of P116.02. Moreover, the number of
motor pole pairs (P109) has to be an integer multiple of
the value of P116.02. If one of these two conditions is not
satisfied, fault F061 with fault value 116 is set upon exiting
the drive settings.
index1: 1
Min: -110
Max: 110
Unit: -
Indices: 2
Type: I2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Quick parameterization
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P117
Kp-Adapt.
117
Corner points for describing the linear adaption of the gain
factor Kp of the current controller as a function of the
curve of the inductivity of the synchronous machine.
Index 1: Value of current at which the linear reduction
begins (up to which the inductivity has the value of P120.1)
Index 2: Value of current at which the linear reduction
ends (from which the inductivity has the value of P120.2)
index1: 0,00
Min: 0,00
Max: 1300,00
Unit: A
Indices: 2
Type: I4
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P119*
Ratio Lq/Ld
119
Function parameter for entering the ratio of
the mutual inductance transversal to the rotor-axis (Lq)
to the mutual inductance along the rotor-axis (Ld)
of a connected synchronous motor.
The parameter value is calculated during the automatic
motor data identification of derived motor data (P115).
Init: 0,880
Min: 0,200
Max: 5,000
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P120*
Main Field Induc
120
Function parameter for entering the main field inductance
(in mH) of a connected synchronous motor. The value to
be entered is 1.5 times the inductance of a winding phase
in the star equivalent circuit.
index1: 0,000
Min: 0,000
Max:
2000,000
Unit: mH
Indices: 2
Type: O4
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P121*
Stator Resist
121
Function parameter for entering the stator resistance of a
connected synchronous or induction motor. The value to
be entered corresponds to the ohmic resistance of a
winding phase at 20°C.
index1: 0
Min: 0
Max: 50000
Unit: mOhm
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P122*
Tot Leak React
122
Function parameter for entering the total leakage
reactance of a connected induction motor. The value to be
entered corresponds to the total leakage reactance of a
winding phase. The parameter value is calculated during
the automatic calculation of derived motor data (P115).
index1: 0
Min: 0
Max: 65535
Unit: mOhm
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
15
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control
Содержание simovert masterdrives
Страница 1: ...Compendium Edition AN simovert masterdrives Motion Control ...
Страница 2: ......
Страница 13: ......
Страница 197: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 32 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 199: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 34 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 201: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 36 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 203: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 38 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 205: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 40 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 207: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 42 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 209: ...Parameterizing Steps 08 2012 6SE7087 6QX70 Version AN Siemens AG 6 44 Compendium Motion Control SIMOVERT MASTERDRIVES ...
Страница 947: ...08 2012 Siemens AG 6SE7087 6QX70 Version AN SIMOVERT MASTERDRIVES Compendium Motion Control Function Diagrams ...
Страница 1160: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control General parameter list ...
Страница 1416: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control Connector list ...
Страница 1446: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control Binector list ...
Страница 1466: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control List of function data set parameters ...
Страница 1471: ...03 2010 Siemens AG 6SE7087 6QX70 Version AL SIMOVERT MASTERDRIVES Compendium Motion Control List of binector data set parameters ...
Страница 1535: ......
Страница 1536: ......
Страница 1537: ......
Страница 1538: ......
Страница 1539: ......
Страница 1540: ......
Страница 1541: ......
Страница 1542: ......
Страница 1543: ......
Страница 1546: ......