Online Settings and Displays
17.11 Warnings
SIMOCODE PRO V PN FDI
162
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Indication
Meaning/Possible cause/Acknowledgement/Error processing
Warning level P>
The real power of the motor has overshot theWarning level.
Check the application which is driven by the motor.
Further information: Active Power Monitoring (Page 55).
Warning level P<
The real power of the motor has undershot the Warning level.
Check the application which is driven by the motor.
Further information: Active Power Monitoring (Page 55).
Warning level U<
The voltage in the motor feeder has undershot the Warning level.
Possible causes:
•
Undervoltage in the network
•
Fuse has tripped.
Check the motor feeder.
Further information: Voltage Monitoring (Page 52).
Warning level Cos-Phi<
The power factor has undershot the Warning level.
Possible cause: The motor is operated without a load.
Check the application which is driven by the motor.
Further information: Cos-Phi Monitoring (Page 54).
Warning level 0/4-20 mA>
The measured value on the analog input has overshot the
Warning level.
Check the measuring station.
Further information: 0/4-20 mA Signal Monitoring (Page 60).
Warning level 0/4-20 mA<
The measured value on the analog input has undershot the
Warning level.
Check the measuring station.
Further information: 0/4-20 mA Signal Monitoring (Page 60).
No. of starts>
The permitted number of starts in the monitoring time frame was
exceeded. The next start should not be carried out until the
interlocking time has expired.
Further information: Monitoring the Number of Starts (Page 64).
Just one start possible
The start after the next one should not be carried out until the
interlocking time has expired.
No start possible
The permitted number of starts in the monitoring time frame was
achieved. The next start should not be carried out until the
interlocking time has expired.
Acknowledge with "Reset".
Motor operating hours >
The configured limit value for the motor operating hours has been
exceeded.
Implement the maintenance measures planned for the feeder.
Motor stop time >
The configured limit value for the stopped time has been
exceeded.
Implement the maintenance measures planned for the feeder. If
possible, switch on the feeder.