Logic Modules
13.9 Calculation Modules
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
127
13.9
Calculation Modules
13.9.1
Calculation Modules
Calculation Modules
Calculation Modules 1 and 2
Both the Calculator 1 and Calculator 2 logic modules integrated in Basic Unit 2 contain the
standard calculation modes and enable all analog values that occur in SIMOCODE pro to be
adapted, calculated and converted, e.g.
●
Conversion of the measured temperatures from K (Kelvin) to °F or °C
●
Conversion of the motor current from % to A
●
Conversion of the 0/4 - 20 mA signals of the Analog Module directly into fill levels,
pressures and flow rates.
The analog value (2 Byte/1 Word) present at the analog socket is calculated using a defined
formula and using freely-selectable parameters (counters, denominators, operators, offsets).
The result of the calculation is output as an analog value at the analog socket of the logic
module (2 Bytes/1 Word) for further processing.
Each Calculator consists of:
●
1 analog plug (Calculator 1) or two analog plugs (Calculator 2)
●
1 logic component
●
1 analog socket (Calculation Module Output).
Formula Calculator 1
Formulas Calculator 2
●
Operation mode 1: Both inputs of type word.
●
Operation mode 2: Inputs 1 and 2 correspond to a D-word input.
●
Offset value range: - 2147483648 to 2147483647, increment 1.