Standard Functions
12.6 Emergency Start
SIMOCODE PRO V PN FDI
96
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
12.6
Emergency Start
Emergency Start
The emergency start deletes the thermal memory from SIMOCODE pro each time it is
activated. This enables immediate restarting of the motor after an overload trip. This function
can be used to:
●
Enable a reset and start up the motor again immediately after an overload trip.
●
Delete the thermal memory (motor model) during operation, if required.
Note
Frequent emergency starts may result in thermal overloading of the motor.
An emergency start is carried out via the plug of the function block. To do this, the input
(plug) of the function block must be connected to any socket (e.g. device inputs, control bits
from PROFINET, etc.).
The Emergency Start function block consists of:
●
1 plug
●
1 "Status - Emergency Start Executed" socket. This is set when the emergency start is
carried out.
Overall, there is 1 Emergency Start function block for BU1 and BU2.
Settings Emergency Start
Control of the Emergency Start function block from any signal (any sockets, e.g. device
inputs, control bits from PROFINET, etc.).