Monitoring Functions
9.9 Monitoring - Interval for Mandatory Testing
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
67
9.9
Monitoring - Interval for Mandatory Testing
Monitoring - Interval for Mandatory Testing
Function for monitoring the interval between the connection and the tripping of the enabling
circuit (actuator tripping). The monitoring time starts anew, every time the enabling circuit
closes.
This function supports you in complying with test intervals that require verification.
In the enabling circuit of the DM-F Local and the DM-F PROFIsafe, relay contacts carry out
safety-oriented tripping. Whether the relay contacts of the enabling circuit really open or not,
can only be established via a change in the switching state of the contacts.
The "Monitoring - interval for mandatory testing" function supports the system operator in the
monitoring of the time that has elapsed since the last connection of the enabling circuit.
When the adjustable limit has been reached, the set reaction follows (deactivated, send,
warning; see response). This is logged in the event memory.
This monitoring function is an organizational measure that supports the system operator in
detecting faults by carrying out regular testing. It is comparable with the notes in the
operating instructions for regularly testing of the function of a safety device. Die The
monitoring function itself need not be safety-oriented.
Response "Monitoring - interval for mandatory testing"
Here you can determine the response when the set limit value is reached:
Response
Monitoring - interval for mandatory testing
Disabled
X
Signaling
X
Warning
X
Tripping
-
Test interval (CiR)
Adjustable limit value for interval for mandatory testing: 0 - 255 weeks.