Outputs
11.5 Analog Module Outputs
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
79
Application examples
●
Controlling the motor contactor in the motor feeder:
You can e.g. define which relay output is used for controlling the motor contactor in the
motor feeder. For this, connect the desired relay output to the respective "QE" contactor
control of the control function.
●
Lamp control for displaying operating states:
You can e.g. define which relay outputs are to be used for controlling the lamps/LEDs
displaying operating states of the motor (FAULT, ON, OFF, FAST, SLOW...).
For this, connect the desired relay output to the respective "QE..." Lamp Control of the
control function.
●
Transfer of any other information, status information, warnings, faults, etc. to the relay
outputs.
Settings Digital Module 2 Outputs
Control of the DM2 outputs function block with any signal (any sockets, e.g. device inputs,
control bits from PROFINET, etc. usually from the QE contactor controls).
11.5
Analog Module Outputs
Analog Module Outputs
You can use analog modules 1 and 2 to expand basic unit 3 with one analog input each. The
corresponding function blocks "AM1 Output" and "AM2 Output" (in conjunction with
SIMOCODE pro V PN basic unit only) allow every analog value (2 bytes/1 word) in
SIMOCODE pro to be output as a 0/4 A - 20 mA signal, for example, on a connected pointer
instrument. By activating the function block via the "assigned analog output value" plug with
any integer value between 0 and 65535, an equivalent analog signal of 0 to 20 mA or 4 to 20
mA will be sent to the output terminals of the Analog Module.
Note
The AM1 Output and AM2 Output function blocks can only be used if the respective analog
module (AM) is connected and configured in the device configuration!