Standard Functions
12.7 Safety Oriented Tripping
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
105
"Safe tripping" response 1)
Here, you set the SIMOCODE pro reaction to a safety-oriented tripping via the DM-F Local
or the DM-F PROFIsafe.
Note
The module response is not affected by this setting. In the event of the conditions for safety-
oriented tripping being fulfilled, the enabling circuits are always opened!
Response
Safe tripping
Tripping
X
Disabled
X
Send
X
Warning
X
Note
In the event that the option "DM-F LOCAL/PROFIsafe - separate function from control
function" has been activated under "Motor control > Control function > Operating mode",
"Tripping" can no longer be set as response; "Deactivated", "Send" or "Warning" are the only
remaining options.
Reset "Safe tripping"
Here, you can select manual or automatic acknowledging of SIMOCODE pro faults caused
by safety-oriented tripping (default: manual).