Motor Control
8.3 Control Function
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
37
8.3.2
Operating Mode
Operating Mode
Parameter
Description
Non-maintained command mode
•
Deactivated:
The control command on the corresponding input of
the control stations "ON <, ON <<, ON >,ON >>" is
saved. It can only be revoked by an "OFF" control
command from the corresponding control station.
The auxiliary contact for locking the contactor is no
longer necessary. Motor feeders are usually operated
in locking mode. Locking is preset.
•
Activated:
Depending on the control function chosen, the Non-
maintained command mode affects the plugs of all
control stations "ON <, ON <<, ON >, ON >>".A
control command is only effective as long as there is
a "high signal".
Saving change-over Command
•
Deactivated:
Commands for switching from one direction of
rotation/rotational speed to the other are
implemented with a previous "OFF" and after the
interlocking time/change-over pause has elapsed.
This setting is usually used and is preset.
•
Activated:
Commands for switching from one direction of
rotation/rotational speed to the other are
implemented without a previous "OFF" and after the
interlocking time/change-over pause has elapsed. If
the selected direction/speed cannot be executed
immediately due to a parameterized interlocking
time/change-over pause, the selection is signalized
by flickering QLE displays. Your selection can be
cancelled at any time with "OFF".