Service and maintenance
10.2 Error messages
SIMATIC RF166C
138
Operating Instructions, 12/2019, C79000-G8976-C578-01
"ER"
LED
Block (hex)
Error description
4x
0xE4FE8C00
•
Communication error between Ident profile and communication module. Handshake error.
Possible causes / action to be taken:
–
The UDT of this communication module has been overwritten by other program sections.
–
Check the parameter settings of the communication module in the UDT.
–
Check the Ident profile command that causes this error.
–
After eliminating the error, execute the "INIT" command.
•
Backplane bus / PROFIBUS DP error occurred.
This error is only indicated when access monitoring has been enabled in the PROFIBUS con-
figuration.
Possible causes / action to be taken:
–
Backplane bus / PROFIBUS DP bus connection was interrupted (wire break on the bus;
bus connector on the communication module was briefly unplugged)
–
The backplane bus / PROFIBUS DP master no longer addresses the communication
module
–
Execute the "INIT" command.
–
The communication module has detected a frame interruption on the bus. The backplane
bus, PROFIBUS may have been re-configured (e.g. with HW Config or TIA Portal)
--
0xE4FE8D00
•
Firmware error
Possible causes:
The firmware update was not run completely.
•
Internal communication error of the communication module/reader
Possible causes / action to be taken:
–
Connector contact problem on the communication module / reader
–
Hardware of the communication module/reader has a defect;
→
Send in communication
module/reader for repair.
–
After eliminating the error, execute the "INIT" command.
•
Internal monitoring error of the communication module/reader
Possible causes / action to be taken:
–
Program execution error on the communication module / reader
–
Switch supply voltage to communication module/reader off and on again.
–
After eliminating the error, execute the "INIT" command.
--
0xE4FE8E00 The current command was aborted by the "WRITE-CONFIG" ("INIT" or "SRESET") command for
the bus connector was pulled.
Possible causes:
•
Communication with the transponder was aborted by "INIT".
•
This error can only be reported if there is an "INIT" or "SRESET".
--
0xE5FE0100 Incorrect sequence number order (SN) on the reader/communication module
--
0xE5FE0200 Incorrect sequence number order (SN) in the Ident profile
--
0xE5FE0400 Invalid data block number (DBN) on the reader/communication module
--
0xE5FE0500 Invalid data block number (DBN) in the Ident profile
Содержание SIMATIC RF166C
Страница 6: ...Table of contents SIMATIC RF166C 6 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 14: ...Security recommendations SIMATIC RF166C 14 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 20: ...Description 3 3 Design SIMATIC RF166C 20 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 98: ...Programming via SIMATIC controller SIMATIC RF166C 98 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 156: ...Service and maintenance 10 5 Module replacement SIMATIC RF166C 156 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 160: ...Dimensional drawings SIMATIC RF166C 160 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 176: ...Service Support SIMATIC RF166C 176 Operating Instructions 12 2019 C79000 G8976 C578 01 ...