Supplementary information
18.16 CPU 410 cycle and reaction times
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
371
Calculation of the actual cycle time
●
Allowance for communication load (default value: 20%):
18.419 ms * 100 / (100–20) = 23.024 ms.
●
There is no interrupt processing.
So the actual, cycle time is approx. 23 ms.
Calculating the longest response time
●
Longest response time
23.024 ms * 2 = 46.048 ms.
●
The delay of the inputs and outputs is negligible.
●
All the components are plugged into the central controller; DP cycle times do not
therefore have to be taken into account.
●
There is no interrupt processing.
So the longest, rounded up response time is = 46.1 ms.
Example II
You have installed an S7-400 with the following modules:
●
a CPU 410–5H in redundant mode
●
4 digital input modules SM 421; DI 32×DC 24 V (each with 4 bytes in the PI)
●
3 digital output modules SM 422; DO 16xDC 24 V /2 (each with 2 bytes in the PI)
●
2 analog input modules SM 431; AI 8x13 bit (not in the PI)
●
2 analog output modules SM 432; AO 8x13 bit (not in the PI)
CPU parameters
The CPU parameters were assigned as follows:
●
Cycle load due to communication: 40%
User program
According to the instruction list, the user program runtime is 10.0 ms.