Technical data
16.1 Technical specifications of CPU 410-5H; (6ES7410-5HX08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
258
System Manual, 05/2017, A5E31622160-AC
Article number
6ES7410-5HX08-0AB0
Autocrossing
Yes
System redundancy
Yes
Redundant subnetworks
Yes
Change of IP address at runtime, supported
No
Number of connection resources
120
Interface types
•
Number of ports
2
•
integrated switch
Yes
Media redundancy
•
supported
Yes
•
Switchover time on line break, typ.
< 200 ms
•
Number of stations in the ring, max.
50
Functionality
•
PROFINET IO Controller
Yes
•
PROFINET IO Device
No
•
PROFINET CBA
No
•
Open IE communication
Yes
•
Web server
No
PROFINET IO Controller
•
Transmission rate, max.
100 Mbit/s
Services
–
PG/OP communication
Yes
–
S7 routing
Yes
–
S7 communication
Yes
–
Open IE communication
Yes
–
Shared device
No; however, usable as part of S7
–
Prioritized startup
No
–
Number of connectable IO Devices,
max.
250
–
Number of connectable IO Devices for
RT, max.
250
–
of which in line, max.
250
–
Activation/deactivation of IO Devices
Yes; Single mode only
–
IO Devices changing during operation
(partner ports), supported
No
–
Device replacement without swap me-
dium
Yes
–
Send cycles
250 µs, 500 µs, 1 ms, 2 ms, 4 ms