Plant changes in RUN - CiR
11.9 Reconfigure existing modules in ET200M / ET200iSP stations
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
189
Procedure for changing the user program and the hardware
The user program and the hardware must be changed as a result of the re-configuration.
This is the case, for example, when you re-configure an input channel from "0 to 20 mA" to
"0 to 10 V".
1.
Set the values of the channel being re-configured to simulation (in the associated driver).
2.
Change the associated hardware.
3.
Change the hardware configuration and download it to the CPU.
4.
Save your project.
5.
If necessary, adapt the user program to the changed channel and download it to the
CPU.
Cancel the simulation for the re-configured channel (in the corresponding driver).
Procedure for changing the address area of the ET 200iSP electronic module
This is the case, for example, when you use IEEE values of a HART electronic module.
Follow these steps:
1.
Set the values of the module being re-configured to simulation (in the associated driver).
2.
Delete the module in the hardware configuration and download it to the CPU.
3.
Insert the module once again and configure it for your configuration as needed.
4.
Download the hardware configuration to the CPU.
5.
Save your project.
6.
If necessary, adapt the user program to the changed module and download it to the CPU.
7.
Cancel the simulation for the re-configured module (at the associated driver).
11.9.4.3
Delete an already used channel.
Procedure
You do not need to change the hardware configuration if you no longer need a channel
previously used.
1.
Change the user program so that the channel to be removed is no longer evaluated, and
download it to the CPU.
2.
Change the hardware configuration and download it to the CPU.
3.
Save your project.
4.
Change the corresponding hardware (remove sensor or actuator, etc.).