Configuration of the CPU 410
3.2 CPU 410 monitoring functions
CPU 410 Process Automation/CPU 410 SMART
40
System Manual, 05/2017, A5E31622160-AC
Type of error
Cause of error
Error LED
Failure of a rack/station
•
Power failure in an S7-400 expansion unit
•
Failure of a DP/PN segment
•
Failure of a coupling segment: Missing or defective IM, inter-
rupted cable
EXTF
BUSF for PN and DP
REDF for redundant
segments
Communication error
Communication error:
•
Time synchronization
•
Access to DB when exchanging data via communications func-
tion blocks
INTF
Execution canceled
The execution of a program block was canceled. Possible reasons
for the cancellation are:
•
Nesting depth of nesting levels too great
•
Nesting depth of master control relay too great
•
Nesting depth of synchronization errors too great
•
Nesting depth of block call commands (U stack) too great
•
Nesting depth of block call commands (B stack) too great
•
Error during allocation of local data
Such errors cannot occur with blocks from a SIMATIC PCS 7 li-
brary.
INTF
Missing license for Runtime
software
The Runtime software could not be completely licensed (internal
error).
INTF
Programming error
User program error:
•
BCD conversion error
•
Range length error
•
Range error
•
Alignment error
•
Write error
•
Timer number error
•
Counter number error
•
Block number error
•
Block not loaded
Such errors cannot occur with blocks from a SIMATIC PCS 7 li-
brary.
INTF
MC7 code error
Error in the compiled user program, for example, illegal OP code or
a jump beyond the block end
Such errors cannot occur with blocks from a SIMATIC PCS 7 li-
brary.
INTF