Plant changes in RUN - CiR
11.6 Permitted changes over PROFIBUS DP
CPU 410 Process Automation/CPU 410 SMART
168
System Manual, 05/2017, A5E31622160-AC
The following OBs must be available in your CPU:
●
Hardware interrupt OBs (OB 40 to OB 47)
●
Cycle time error OB (OB 80)
●
Diagnostic interrupt OB (OB 82)
●
Remove/insert interrupt OB (OB 83)
●
Program execution error OB (OB 85)
●
Rack failure OB (OB 86)
●
I/O access error OB (OB 122)
Note
These requirements are always met with SIMATIC PCS 7.
11.6
Permitted changes over PROFIBUS DP
Permitted configuration changes: Overview
The method presented here supports the following modifications in your automation system:
●
Addition of modules for a modular DP slave, provided you have not integrated it as a
DPV0 slave (via a GSD file).
●
Reassignment of module parameters, e.g. selection of different alarm limits or use of
previously unused channels
●
Replacement of standby modules with future electronic modules of the ET 200iSP
●
Reassignment of parameters of ET 200iSP modules
●
Addition of DP slaves to an existing DP master system
●
Addition of PA slaves (field devices) to an existing PA master system
●
Addition of DP/PA couplers downstream of an IM 157
●
Addition of DP/PA links (including PA master systems) to an existing DP master system
●
Assignment of added modules to a process image partition
●
Modification of the process image partition assignment for existing modules or compact
slaves