Configuration of the CPU 410
3.5 PROFINET IO interfaces (X5, X8)
CPU 410 Process Automation/CPU 410 SMART
46
System Manual, 05/2017, A5E31622160-AC
Connectors
The PROFINET interfaces are implemented as Ethernet RJ45 interfaces. Always use RJ45
connectors to hook up devices to a PROFINET interface.
Properties of the PROFINET IO interfaces
Protocols and communication functions
PROFINET IO
According to IEC 61784-2
Conformance Class A und B
Open block communication over
•
TCP
•
UDP
•
ISO-on-TCP
S7 communication
Yes
PG functions
Yes
Port statistics of PN IO devices (SNMP)
Yes
Detection of the network topology (LLDP)
Yes
Media redundancy (MRP)
Yes
Time synchronization in NTP method as client
Yes
Time synchronization in SIMATIC method
Yes
Time synchronization in pTCP method
Yes
You can find further information about the properties of the PROFINET IO interfaces in the
technical specifications of the CPUs in section Technical data (Page 253).
Connection per interface
Version
2 x RJ45
Switch with 2 ports
Media
Twisted pair Cat5
Transmission rate
10/100 Mbps
Autosensing
Autocrossing
Autonegotiation