Technical data
16.2 Technical specifications of CPU 410E (6ES7410-5HM08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
270
System Manual, 05/2017, A5E31622160-AC
Article number
6ES7410-5HM08-0AB0
–
Open IE communication
Yes
–
Shared device
No; however, usable as part of S7
–
Prioritized startup
No
–
Number of connectable IO Devices,
max.
250
–
Number of connectable IO Devices for
RT, max.
250
–
of which in line, max.
250
–
Activation/deactivation of IO Devices
Yes; Single mode only
–
IO Devices changing during operation
(partner ports), supported
No
–
Device replacement without swap me-
dium
Yes
–
Send cycles
250 µs, 500 µs, 1 ms, 2 ms, 4 ms
–
Updating time
250 µs to 512 ms, minimum value depends on
the number of configured user data and the con-
figured single or redundant mode
Address area
–
Inputs, max.
1 536 byte; Up to 1 500 IOs (channels)
–
Outputs, max.
1 536 byte; Up to 1 500 IOs (channels)
–
User data consistency, max.
1 024 byte
Open IE communication
•
Number of connections, max.
118
•
Local port numbers used at the system end 0, 20, 21, 25, 102, 135, 161, 34962, 34963,
34964, 65532, 65533, 65534, 65535
•
Keep-alive function, supported
Yes
4. Interface
Interface type
Pluggable synchronization submodule (FO)
Plug-in interface modules
Synchronization module 6ES7960-1AA06-0XA0,
6ES7960-1AB06-0XA0 or 6ES7960-1AA08-0XA0
5. Interface
Interface type
Pluggable synchronization submodule (FO)
Plug-in interface modules
Synchronization module 6ES7960-1AA06-0XA0,
6ES7960-1AB06-0XA0 or 6ES7960-1AA08-0XA0
Protocols
Supports protocol for PROFINET IO
Yes
PROFINET CBA
No
PROFIsafe
Yes
PROFIBUS
Yes
AS-Interface
Yes; Via add-on
Protocols (Ethernet)
•
TCP/IP
Yes