Tips for Integrating with an OPC client
83
Building Technologies
048_DMS_MK8000_ICC_MP4.30_A6V10062407_a_en
Fire Safety & Security Products
06.2010
Endpoints tab - MM8000Server Properties
We recommend leaving the Endpoints level to Default. This means that this
server will use the protocols that were set up on the Default Properties tab in
the DCOM Config utility. The Endpoints tab should look like Fig. 83:
Fig. 83 MM8000Server Properties - Endpoints tab
Identity tab - MM8000Server Properties
This tab is used to determine which account you want to use to run the applica-
tion. There are four choices that the system uses to determine which account
your DCOM object will run under:
The Interactive User: the application will run using the security context of the
user currently logged onto the computer. If this option is selected and the
user is not logged on, then the application will not start.
The Launching User: the application will run using the security context of the
user who started the application. The launching user and the interactive user
may be the same (recommended).
This User: you may specify the user whose security context will be used to
run the application.
The System Account: this is available only for services that use DCOM.
Set the Identity as shown in Fig. 84 (Launching User):