Testing the Configuration
67
Building Technologies
048_DMS_MK8000_ICC_MP4.30_A6V10062407_a_en
Fire Safety & Security Products
06.2010
Fig. 68 Server Address Space Dialog Window
2.
Verify that all the subsystems are displayed in this list.
Note: The subsystem names that are displayed here correspond with the OPC
group names entered in the MK8000 tab of composer during the configuration
process (see section 4.8, p.60).
3.
Use the
Add Branch
button to insert subsystems into the main window for test-
ing, and select
Done
when finished.
The subsystems appear in the main window of the client.
Note:
The OPC Test Client performs best with less than 5000 points attached
at a time. Therefore it is recommended that you test a few branches at a time
rather than testing everything all at once.
Starting the subsystems, and verifying value and quality
To start the subsystems, and verify their values and qualities, do the following:
1.
Select and start the subsystems one by one with the start icon
, -- or --
Start all the subsystems at once with the start-all icon
.
The subsystem nodes change to yellow.
2.
Verify that the top OPC object of a subsystem is yellow with value: Fault Ack
(1999), and Quality: GOOD.
Note
: Do this step while still disconnected from the subsystems.
3.
Verify that the child nodes of the top object are grey with value: Quiet (1000),
Quality: BAD. (See Fig. 69.)
4.
Repeat steps 2 and 3 for each subsystem.