Testing the Configuration
66
Building Technologies
048_DMS_MK8000_ICC_MP4.30_A6V10062407_a_en
Fire Safety & Security Products
06.2010
Fig. 66 Client options
If you are connecting to the server from a remote client, then select the
Re-
mote Connection
box and select the station where the server resides.
If your OPC Client supports a limited number of characters for objects, then
check the
Use short item name
box (names will be limited to 50 charac-
ters).
Next option concerns the number of items per object, which can be one or
three. If your OPC Client cannot access the
OPC
item vendor specific prop-
erties (containing command information) and you will handle the item com-
mands with two more separate items, then check the
Use new mode
for
command items.
Finally, you have to select the multi-state mode, which can be numeric
(threshold) or bit oriented (bit-mask). Default is numeric mode, check the Bit-
mask mode checkbox if you want to change it.
Click
OK.
The MK8000 server appears in the left pane (see Fig. 67).
Fig. 67 Connecting to the MK8000 Server
Checking that all subsystems are present, and adding them to the client
To verify that all subsystems are present, and add them to the client, do the follow-
ing:
1.
Open the Server Address Space dialog window with the Browser Server
icon.