3-20
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The bus lines (see Appendix A) are connected to the plug-in, multipole
screw-type terminal.
Note
When you remove the PROFIBUS-DP screw-type terminal, the subsequent
DP slaves are disconnected from the PROFIBUS-DP.
1. Strip the insulation from the bus line as shown in the figure below.
22 mm
7 mm
6.5 mm
Figure 3-10 Length of Insulation Stripped
2. Connect the bus line to the screw-type terminal, and screw the cover on
the holder.
Cover
Holder
Shield
Bus line
IN
Bus line
OUT
Shield support
IM-SC
Figure 3-11 Wiring the PROFIBUS-DP Screw-Type Terminal
3. Insert the screw-type terminal in the appropriate socket on the IM-SC
interface module.
Wiring the
PROFIBUS-DP
Connection
Wiring
Содержание Metro 21 M216KA