C-27
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
C.4.6
Parameterization Frame Example
The example below describes the parameterization of an
ET 200L-SC IM-SC.
The Smart Connect contains the following electronic modules:
2DIDC24V (slot A)
2DODC24V0.5A (slot B)
2AI U (slot C)
1AO I (slot D)
1COUNT40kHz (slot F)
Table C-13 below shows the contents of the associated parameterization
frame:
Table C-13
ET 200L-SC IM-SC Example
Byte
Value
Meaning
0 to 6
See Figure
C-2
Standard section
7
40
H
Status byte 0
Status bytes
8
20
H
Status byte 1; diagnostic interrupt enable: 21
H
y
9
00
H
Status byte 2
10
07
H
Block length
Data record 0
(digital)
11
5F
H
S7 constant
(digital)
12
04
H
Slot
13
00
H
Data record number
14
02
H
Data record length
15
00
H
Diagnostics enable: 0
16
00
H
Not applicable
17
15
H
Block length
Data record 128
(digital)
18
5F
H
S7 constant
(digital)
19
04
H
Slot
20
80
H
Data record number
21
10
H
Data record length
22
00
H
Version identifier
23
50
H
Additional identifier/device type assignment
Example
Configuration Frame and Parameterization Frame for the ET 200L
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...