B-4
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Table B-3 indicates the maximum number of inputs and outputs of the differ-
ent ET 200L electronics blocks:
Table B-3
Maximum Number of Inputs and Outputs with the ET 200L
Electronics Block
Maximum Number of
Inputs (Bytes)
Outputs (Bytes)
Inputs and Outputs
Together (Bytes)
L 16 DI DC 24 V
2
0
2
L 32 DI DC 24 V
4
0
4
L 16 DO DC 24 V/0.5 A
0
2
2
L 32 DO DC 24 V/0.5 A
0
4
4
L 16 DI/16 DO DC 24 V/0.5 A
2
2
4
Table B-4 indicates the maximum number of inputs and outputs of the differ-
ent ET 200L-SC electronics blocks.
Table B-4
Maximum Number of Inputs and Outputs with the ET 200L-SC or ET 200L-SC IM-SC
Electronics Block
Maximum Number of Digital
1
Maximum Number of Analog
2
Inputs
(Bytes)
Outputs
(Bytes)
Inputs and
Outputs
Together
(Bytes)
Inputs
(Bytes)
Outputs
(Bytes)
Inputs and
Outputs
Together
(Bytes)
Type File with SI802XA?.200
3,4
Type File with SI802XB?.200
3,4
L-SC 16 DI DC 24 V
10
8
18
34
32
66
L-SC 32 DI DC 24 V
12
8
20
36
32
68
L-SC 16 DO DC 24 V/0,5 A
8
10
18
32
34
66
L-SC 16 DI/16 DO DC 24 V/0,5 A
–
–
–
34
34
68
L-SC IM-SC
64
64
128
–
–
–
1
Only digital input and output modules are connected to the ET 200L-SC.
2
Analog and digital input and output modules are connected to the ET 200L-SC; you can use digital or analog or digital
and analog modules on the Smart Connect.
3
“X” = 7, 8, 9 or C
4
“?” stands for a language abbreviation; D = German
Inputs and
Outputs with the
ET 200L
Inputs and
Outputs with the
ET 200L-SC or
ET 200L-SC IM-SC
Type and Device Master Files
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...