2-20
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
In analog processing, you insert the cables of the signal lines in the shield
terminal. To do this, proceed as follows:
1. Clip the TB 16IM-SC/TB 16SC terminal block onto the rail.
2. Connect a 1- or 2-tier supplementary terminal to the TB 16IM-SC/
TB 16SC terminal block.
3. Connect the metallic shield terminal to the 1- or 2-tier supplementary ter-
minal.
Figure 2-12 Connecting a Shield Terminal to the Supplementary Terminal
Shielding for
Analog Processing
Installation
Содержание Metro 21 M216KA