12-22
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The 2 AI I electronic module uses the following parameters:
Table 12-4
Static Parameters of the 2 AI I Electronic Module
Parameter
Value Range
Default Parameters
Scope
Measurement type
Deactivated
Current (4-wire measuring
transducer)
Current (4-wire measuring
transducer)
Channel
Measurement range (4-wire
measuring transducer)
4...20 mA
"
20 mA
4...20 mA
Channel
Interference frequency sup-
pression
50 Hz (integration time
60 ms)
60 Hz (integration time
50 ms)
50 Hz
Module
Smoothing
None
Weak
Medium
Strong
None
Channel
Format
SIMATIC S7
SIMATIC S5
SIMATIC S7
Channel
If you have not set the parameters of the 2 AI I electronic module using the
specified software (see Chapter 4), the default settings apply to both input
channels after a restart (see Table 12-3).
Parameters
Default Parameters
SC Analog Electronic Modules – T
echnical Data
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...