10-19
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The technical data of the 1DORel.AC230V
digital electronic module is listed
below.
Dimensions and Weight
Dimensions W
H
D (mm)
10
64
51
Weight
approx. 30 g
Module-Specific Data
Number of outputs
1
Contact type
1 x A
Cable length
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated supply voltage of relay
L+
Reverse polarity protection
DC 24 V
yes
Galvanic isolation
Between channels and SC
bus
Between channel and supply
voltage of the relay
yes
yes
Permissible potential difference
Between ground and supply
voltage of the relay
Between ground or supply
voltage of the relay and the
output
DC 75 V, AC 60 V
AC 240 V
Isolation tested with
Between ground and supply
voltage of the relay
Between ground or supply
voltage of the relay and the
output
AC 1500 V
DC 2500 V
Power input
From supply voltage L+
max. 15 mA
Power loss of the module
typ. 0.7 W
Status, Interrupts, Diagnostics
Status indication
green LED
Interrupts
none
Diagnostic functions
none
Actuator Selection Data
Continuous thermal current
max. 5 A
Minimum load current
1 mA
Switching capacity and lifetime
of the contacts
For resistive load
For inductive load in accor-
dance with
IEC 947-5-1 DC13/AC15
see Table 10-1
see Table 10-1
see Table 10-1
Lamp load
see Table 10-1
Internal contact connection
Varistor
rated voltage 275 V
Parallel switching of 2 outputs
For redundant control of a
load
For performance enhance-
ment
possible
not possible
Controlling a digital input
possible
Switching frequency
Mechanical
With resistive load
With inductive load in accor-
dance with IEC 947-5-1
DC13/AC15
With lamp load
max. 10 Hz
max. 1 Hz
max. 1 Hz
max. 0.1 Hz
max. 0.1 Hz
Technical Data
SC Digital Electronic Modules – Technical Data
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...