8-30
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Voltages, Currents, Potentials
Supply voltage L1
S
Rated voltage
120 VAC
S
Permissible range
74 to 132 VAC
S
Frequency
47 to 63 Hz
S
Power failure
withstand time
At least 20 ms
Aggregate current of outputs (per byte)
S
Horizontal installation
up to 40
_
C
Max. 1 A
up to 60
_
C
Max. 0.4 A
S
All other installation
positions
up to 40
_
C
Max. 0.4 A
Optical isolation
S
Between channels
Yes
S
Between L1 and
PROFIBUS-DP
Yes
S
Between channels and
PROFIBUS-DP
Yes
Insulation tested with
1500 VAC
Power input
S
from supply voltage L
Max. 130 mA
Power loss of module
Typically 12.2 W
Status, Alarms, Diagnostics
Status display
Green LED per channel
Alarms
None
Diagnostic function
Yes
S
Bus monitoring
PROFIBUS-DP
Red ‘‘BF” LED
S
Monitoring of
electronics
power supply
Green ‘‘ON” LED
Sensor Selection Data
Input voltage
S
Rated value
120 VAC
S
With signal 1
74 to 132 VAC
S
With signal 0
0 to 20 VAC
Input current
S
With signal 1
9 to 27 mA
S
With signal 0
0 to 4 mA
Input delay
S
From 0 to 1
2 to 14 ms
S
From 1 to 7
6 to 25 ms
Input characteristic
To IEC 1131-2 Type 2
Connection of 2-wire
BEROs
Possible
Actuator Selection Data
Load voltage L
S
Rated voltage
120 VAC
S
Permissible range
74 to 132 VAC
S
Frequency
47 to 63 Hz
Output voltage
S
With signal 1
At least L (– 1.5V)
Output current
S
With signal 1
Rated value
Permissible range
1.0 A Pilot Duty
0.1 to 1.0 A
S
With signal 0
(residual current)
Max. 2.6 mA
Zero cross inhibit voltage
Max. 60 V
Output delay (with
resistive load)
Max. 20 ms
Size of motor starter
S
Up to 40
_
C
Max. size 4 acc. to NEMA
S
Up to 60
_
C
Max. size 3 acc. to NEMA
Lamp load
Max. 50 W
Parallel connection of two outputs
S
For redundant control
of load
Possible
S
For performance
improvement
Not possible
Driving a digital input
Possible
Switching frequency
S
Resistive load
Max. 10 Hz
S
Inductive load
Max. 0.5 Hz
S
Lamp load
Max. 1 Hz
Short-circuit protection
No
ET 200L Electronics Blocks – Technical Data
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...