10-16
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The technical data of the 1DOAC120/230V1A electronic module is listed
below.
Dimensions and Weight
Dimensions W
H
D (mm)
10
64
51
Weight
approx. 15 g
Module-Specific Data
Number of outputs
1
Cable length
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L1
Permissible frequency range
AC 120/230 V
47...63 Hz
Galvanic isolation
Between channels and SC
bus
yes
Permissible potential difference
Between ground and the out-
put
AC 240 V
Isolation tested with
DC 2500 V
Power loss of the module
typ. 0.7 W
Status, Interrupts, Diagnostics
Status indication
green LED
Interrupts
none
Diagnostic functions
none
Actuator Selection Data
Output voltage
At signal ”1”
min. L (1 V)
Output current
At signal ”1”
–
Rated value
–
Permissible range for
0
0
C to 40
0
C
–
Permissible range for
40
0
C to 60
0
C
–
Permissible surge current
At signal ”0”(residual cur-
rent)
1 A
40 mA ... 1.1 A
40 mA ... 0.6 A
max. 10 A (for 2
half-waves)
max. 3 mA
Output delay (with resistive load)
At ”0” to ”1”
At ”1” to ”0”
max. 20 ms
max. 20 ms
Zero crossing
with zero crossing
switch
Size of the motor starter
max. size 8
Lamp load
At AC 230 V
At AC 120 V
max. 100 W
max. 50 W
Parallel switching of 2 outputs
For redundant control of a
load
For performance enhance-
ment
possible
not possible
Controlling a digital input
only possible with
additional load
Switching frequency
With resistive load
With inductive load in accor-
dance with
IEC 947-5-1, AC 15
With lamp load
max. 50 Hz
max. 10 Hz
max. 1 Hz
Short-circuit protection of the
output
no
Technical Data
SC Digital Electronic Modules – Technical Data
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...