11-36
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
System
Temperature Range for Thermocouples
Standard (1 Digit = 0.1
o
C)
Dec.
Hex.
Type R
Type J
Type K
32767
7FFF
Overflow
*2019
o
C
*1450
o
C
*1622
o
C
Overrange
g
1769
o
C
1200
o
C
1372
o
C
Rated range
g
10000
1000
o
C
1000
o
C
1000
o
C
1
1
0.1
o
C
0.1
o
C
0.1
o
C
0
0
0.0
o
C
0.0
o
C
0.0
o
C
– 1
FFFF
– 0.1
o
C
–0.1
o
C
– 0.1
o
C
– 50
o
C
– 210
o
C
– 270
o
C
Underrange
*– 170
o
C
*– 330
o
C
*– 390
o
C
g
– 32768
8000
Underflow
*
Overrange and underrange: In the overrange and underrange, the gradient of the characteristic curve as it leaves the
linearized rated range is retained.
SC Analog Electronic Modules – Parameters
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...