C-25
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The purpose of bytes 12 and 17 of data record 130 for analog input modules
is indicated in Figure C-11.
0
1
7
6 5 4 3
2
Interference suppression
00 – 50 Hz; 01 – 60 Hz
Smoothing
00 – none; 01 – weak
10 – medium; 11 – strong
Temperature reference junction
000 – none; 011 – dynamic reference temperature;
Number format
0 – S7 format; 1 – S5 format
Figure C-11 AI Parameters in Byte 12 or 17 of DS130
The third byte (byte 13 or byte 18) of the channel-specific parameters is al-
ways assigned the value 00
H
for input modules.
The purpose of bits 0 to 5 in bytes 11 and 16 of data record 130 for analog
output modules is indicated in Table C-12.
Bit 6 is always assigned the value “0”.
Bit 7 specifies the number format:
Bit 7 = “0”: S7 format
Bit 7 = “1”: S5 format
Table C-12
AO Parameters in Byte 11 or 16 of DS130
Smart Connect
Module
Output
Measurement Range
Bit
1
Module
p
g
5, 4
3 ... 0
–
Deactivated
00
0000
1AO U
Voltage output
1 ... 5 V
01
0111
g
p
+/– 10 V
1001
1AO I
Current output
0 ... 20 mA
10
0010
p
4 ... 20 mA
0011
1
No other values or combinations are permissible
The second and third bytes (bytes 12 and 13 or bytes 17 and 18) of the chan-
nel-specific parameters are always assigned the value 00
H
for output mod-
ules.
AI Module –
Byte 12 or Byte 17
AI Module –
Byte 13 or Byte 18
AO Module – Byte
11 or Byte 16
AO Module – Bytes
12 and 13 or Bytes
17 and 18
Configuration Frame and Parameterization Frame for the ET 200L
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...