12-28
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The 2 AI HS I electronic module uses the following parameters:
Table 12-5
Static Parameters of the 2 AI HS I Electronic Module
Parameter
Value Range
Default Parameters
Scope
Measurement type
Deactivated
Current (4-wire measuring
transducer)
Current (4-wire measuring
transducer)
Channel
Measurement range (4-wire
measuring transducer)
4...20 mA
"
20 mA
4...20 mA
Channel
Smoothing
None
Weak
Medium
Strong
None
Channel
Format
SIMATIC S7
SIMATIC S5
SIMATIC S7
Channel
If you have not set the parameters of the 2 AI HS I electronic module using
the specified software (see Chapter 4), the default settings of all parameters
apply to both input channels after a restart (see Table 12-3).
Parameters
Default Parameters
SC Analog Electronic Modules – T
echnical Data
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...