7-17
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The figure below shows you the block diagram of the TB 16IM-SC terminal
block.
The connections 3L+ and 3M are used for looping through the load voltage
supply 2L+ and 2M.
1L+
2L+
3L+
A1
...
A4
B1
...
B4
C1
...
C4
H1
...
H4
D1
...
D4
E1
...
E4
F1
....
F4
G1
...
G4
To the IM-SC
1M
2M
3M
Figure 7-7
Block Diagram of the TB 16IM-SC Terminal Block
!
Warning
There is a risk of injury and damage to property.
Connecting different phases of a three-phase system to a terminal block can
lead to injury and damage to property.
Connect only one phase to each terminal block.
Dimensions and Weight
Dimensions W
H
D (mm)
160
100
73.6
Weight
260 g
Module-Specific Data
Number of slots
8
Current-carrying capacity via 1L+ and
2L+
max. 2
8A
Number of times an electronic module can
be plugged into a slot of the TB 16IM-SC
max. 8
Isolation tested
(from slot to slot)
DC 4000 V
Block Diagram
Technical Data
Terminal Blocks and Supplementary Terminals – Technical Data
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...