5-13
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
5.2.5
Structure of the Station Diagnosis for the ET 200L-SC and
ET 200L-SC IM-SC
The station diagnosis provides detailed information about a DP slave.
Data record 0, which is typical of the SIMATIC S7, is stored in the station
diagnosis (bytes 9 to 16).
The contents of the station diagnosis always refer to the Smart Connect sec-
tion.
The station diagnosis contains a maximum of eight bytes. You will find an
explanation of the slots in Appendix C.3.
01
H
01
H
: Code for S7 diagnosis
Byte 9
7
0
Bit no.
Length of station diagnosis
incl. byte 9 (= max. of 8 bytes)
Code for station diagnosis
0 0
Byte 10
01
H
: Code for S7 diagnosis
Byte 11
Slot for ET 200L-SC
05
H
to 9
H
Byte 12
00
H
Reserved
Byte 13
Byte 16
Station diagnosis
for the ET 200L-SC and
ET 200L-SC IM-SC
.
.
Slot for ET 200L-SC IM-SC
04
H,
05
H
Figure 5-5
Structure of Station Diagnosis
Transfer the contents of the station diagnosis to a data block, since the station
diagnosis will be updated periodically.
Definition
Structure
Saving the
Diagnosis
Diagnostics
g
Содержание Metro 21 M216KA
Страница 18: ...xviii ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Contents ...
Страница 34: ...1 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Product Overview ...
Страница 56: ...2 22 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Installation ...
Страница 86: ...4 6 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Commissioning ...
Страница 102: ...5 16 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c Diagnostics g ...
Страница 112: ...6 10 ET 200L ET 200L SC and ET 200L SC IM SC Distributed I O Device EWA 4NEB 780 6009 02c General Technical Data ...