5-4
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Table 5-2
Diagnostics Using the LEDs of the ET 200L-SC or ET 200L-SC IM-SC
SF
LED
(Group
Error)
Error Handling
Meaning
ON LED
BF LED
(Bus Fault)
Off
Flashing
On
ET 200L-SC/ET 200L-SC
IM-SC has still not re-
ceived any configuration
data or has received incor-
rect data.
Bus protocol incorrect
Check the configuration in
the DP master (station
type, input/output,
PROFIBUS address).
Check the format of the
parameterization frame.
On
Error in configuration
frame.
Check the configuration in
the DP master (station
type, input/output,
PROFIBUS address).
Check the configuration of
the configuration frame.